OT Network Monitoring: Start With Plant Floor Switches and Servers

By [email protected] (Michael Becker) 583 views

A failed order server left nine plants down for nearly 12 hours. Monitoring switches and servers can help OT teams find faults faster.

OT Network Monitoring: Start With Plant Floor Switches and Servers

it/ot monitoring podcast what were missing between it and ot

When production stops, teams often check the PLCs and automation systems first. But the fault may sit underneath them: a switch, server or firewall that connects and supports the process. A live discussion on the 4.0 Solutions channel on November 5, 2026, focused on this gap in operational technology (OT) monitoring. Host Walker Reynolds spoke with Eric Eckman, OT Channel Manager, US at Paessler, and David Montoya, Head of Operational Technology at Paessler.

Their point is practical: process monitoring can show that a line stopped, while infrastructure monitoring can help identify why. When nobody is responsible for the network and servers between IT and OT, finding the cause can take far longer than it should.

Plant floor infrastructure can fall between teams

Reynolds estimated that OT infrastructure monitoring happens only 1 to 5% of the time. That figure was his estimate in the discussion, but it underscores a familiar ownership problem. Controls engineers monitor PLCs and HMIs; IT teams look after business networks. Industrial switches and firewalls sit between those responsibilities, and may not have a clear owner.

Eckman said that in his earlier work selling fault-tolerant computers for control rooms, he repeatedly encountered downtime caused by switches or servers. The equipment that connects control systems can be as relevant to production availability as the devices that directly control a process, yet teams may assume the network will simply keep working.

That assumption creates a visibility gap. A SCADA alarm can report that production has stopped, but without infrastructure data alongside process data, it may not reveal whether the initiating fault was a PLC, a network connection or a supporting server. Teams can then spend time investigating the systems they already monitor while overlooking the component that connects them.

A server fault affected nine plants

Montoya described a proof of concept at a large car manufacturer where nine plants went down. Engineers spent almost 12 hours checking PLCs and the automation stack before they traced the issue to a level 3 server in the Purdue model. That server sent production orders to the plants, and an application update had failed.

The server sat in the space between IT and OT, so investigators did not initially look there. Montoya said a SCADA alarm pointing to the server could have directed the team to the fault sooner. Reynolds put average downtime at $120,000 per hour; using that figure, he said the 12 hours represented a substantial cost. The example shows how an unmonitored dependency can stretch both diagnosis and disruption across multiple sites.

For operations teams, the lesson is to include the systems that deliver information to production in the monitoring plan. If a server sends orders or other data to plant systems, its availability and relevant health indicators can matter to production even if it does not run the control logic itself.

Bring infrastructure signals into the process view

Monitoring is more useful when infrastructure and process data can be viewed together. Paessler says PRTG includes sensors for OPC UA, MQTT and Modbus. Its PRTG OPC UA Server extension can send monitoring data from an OT network into supervisory and control systems.

Putting both kinds of data in the same environment can help teams investigate relationships between network conditions and production outcomes. The discussion also connected this approach with a Unified Namespace, where data from different systems is made available in a shared structure. Any such setup depends on the systems and data the organization chooses to connect; the operational aim is to make infrastructure signals available alongside the process signals teams already use.

The episode also raised the possibility of using machine learning to identify links between switch health and poor production outcomes. That depends on having the relevant data together in the first place. For administrators, the immediate step is less ambitious: establish visibility into the network and servers supporting the process, then decide which signals need to reach SCADA or other monitoring tools.

Start with switches and servers

Montoya recommended checking the temperature of switches that connect production cells. Dust and restricted airflow can raise equipment temperatures, and a switch that begins to malfunction can eventually cause PLCs to lose their network connection. Temperature monitoring gives teams an observable condition to investigate before the fault appears as a production interruption.

A broad network discovery may feel intrusive in some OT environments. In that case, the panel suggested limiting an initial scan to the IP addresses of servers and switches. Early checks can reveal issues such as low disk space or TLS certificates that have expired. These findings do not explain every production fault, but they can surface routine infrastructure problems that otherwise stay hidden until a service is affected.

Reynolds shared a separate example from his development board: a Raspberry Pi driver was polling his PLC so frequently that messages were dropped. It illustrates why monitoring and discovery need to account for traffic and device behavior, especially where control communications matter. Teams should review what a scan or polling setup will do on their own network before expanding its scope.

For air-gapped environments, deployment details matter too. The full discussion covered where to place a core server and probes and how to install PRTG without internet access. The recording is available on YouTube.

The practical starting point is clear: identify who owns the switches and servers between IT and OT, monitor their basic health, and make relevant alerts visible to the people responding to production incidents. When the next line stops, that groundwork can help teams check the infrastructure path as well as the control system.

Source: [email protected] (Michael Becker) · blog.paessler.com